Comparison
Four kinds of microreactor, side by side
The four plants in the 3D model use four different ways to move heat out of a small core. Each choice sets the pressure, the temperature, the fuel form, and the kind of safety case the design can make. The table lists the values the model uses. They are typical of each class, not a specific product.
| Feature | Sodium pool (main plant) | Heat pipe | Gas-cooled | Molten salt |
|---|---|---|---|---|
| Coolant | Liquid sodium in a pool | Sodium inside sealed heat pipes | Helium gas | Fluoride salt that also carries the fuel |
| Fuel | HALEU metal or oxide pins in steel cladding | TRISO compacts in a solid block | TRISO particles | Uranium dissolved in the salt |
| Thermal power | ≈ 30 MWt | ≈ 15 MWt | ≈ 15 MWt | ≈ 30 MWt |
| Electric output | ≈ 10 MWe | ≈ 5 MWe | ≈ 5 MWe | ≈ 10 MWe |
| Pressure | Near atmospheric | Near atmospheric | ≈ 7 MPa | Near atmospheric |
| Core outlet temperature | ≈ 550 °C | ≈ 650 °C | ≈ 630 °C | ≈ 650 °C |
| Power cycle | Supercritical CO₂ Brayton | Open-air Brayton | Steam Rankine with salt storage | Steam Rankine |
| Refueling | Whole-core swap every 5 to 10 years | Swap the module after about 8 years | About 20 years on one core | Fuel salt adjusted on line |
| Moving parts in the core loop | Electromagnetic pumps, no impellers | None | One helium circulator | One fuel-salt pump |
| Signature safety feature | Natural-draft air cooling of the vessel | Heat leaves by conduction, no coolant to lose | Fuel coatings hold fission products above 1,600 °C | Freeze plug drains the fuel to a safe tank |
| Where in the model | Main plant, powering the data center | Park plot A, canister open | Park plot B, with two salt tanks | Park plot C, reactor cell |
The sodium pool and the molten-salt designs run hot at low pressure, so they avoid a thick pressure vessel. The gas-cooled design accepts high pressure in return for an inert coolant that cannot boil. The heat-pipe design removes pumps and valves from the core entirely, at the cost of lower power per module.
All four reject their waste heat to air. None of them needs cooling water.